Functions
2.15 Monitoring Functions
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
208
A 3-phase failure of the secondary measured voltages can be distinguished from an actual system fault by
the fact that the currents have no significant change in the event of a failure in the secondary measured voltage.
For this reason, the current values are routed to a buffer so that the difference between present and stored
current values can be analysed to recognise the magnitude of the current differential (current differential crite-
rion), see Figure 2-89.
A three-pole measuring voltage failure is detected if:
• All 3 phase-to-earth voltages are smaller than the threshold FFM U<max (3ph) (address 2913),
• The current differential in all 3 phases is smaller than the threshold FFM Idelta (3p) (address 2914).
If such a voltage failure is recognized, the protection functions whose measuring principle is based on under-
voltage are blocked until the voltage failure is removed; afterwards the blocking is automatically reset.
A three-pole measuring voltage failure is also detected without the mentioned criteria if the signal „VT
FuseFail“ (No. 170) previously has been generated by an asymmetrical measuring voltage failure. The mea-
suring voltage failure is still detected in this state if the three phase-to-earth voltages subsequently fall below
the threshold value FFM U<max (3ph) (address 2913 ).
The effect of the signals „VT FuseFail“ (No. 170) and „VT FuseFail>10s“ (No. 169) on the protection
functions is described in the following section „Effect of the measuring voltage failure“.
Additional Measured Voltage Failure Monitoring „Fail U absent“
If no measuring voltage is available after power-on of the circuit breaker (e.g. because the voltage transformers
are not connected), the absence of the voltage can be detected and reported by an additional monitoring func-
tion. Where circuit breaker auxiliary contacts are used, they should be used for monitoring as well. Figure 2-90
shows the logic diagram of the measured voltage failure monitoring. A failure of the measured voltage is de-
tected if the following conditions are met at the same time:
• All 3 phase-to-earth voltages are less than FFM U<max (3ph),
• At least 1 phase current is larger than PoleOpenCurrent or at least 1 breaker pole is closed (can be set),
• No protection function has picked up,
• This condition persists for a settable time T V-Supervision (default setting: 3 s).
The time T V-Supervision is required to prevent that a voltage failure is detected before the protection picks
up.
If this monitoring function picks up, the indication „Fail U absent“ (no. 168) will be issued. The effect of
this monitoring indication will be described in the following section „Effect of the Measuring Voltage Failure“.

Table of Contents

Other manuals for Siemens SIPROTEC 7SD610

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SD610 and is the answer not in the manual?

Siemens SIPROTEC 7SD610 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SD610
CategoryRelays
LanguageEnglish

Related product manuals