EasyManuals Logo

Siemens SIPROTEC 7SD610 User Manual

Siemens SIPROTEC 7SD610
448 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #209 background imageLoading...
Page #209 background image
Functions
2.15 Monitoring Functions
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
209
Figure 2-90 Logic diagram of the additional measured voltage failure monitoring „Fail U absent“
Effect of the Measuring Voltage Failure
In the event of a measuring voltage failure due to a short-circuit or broken conductor in the voltage transformer
secondary circuit, some or all measuring loops may mistakenly see a voltage of zero. In case that load currents
exist simultaneously, incorrect pickup could occur. If such a voltage failure is detected, the protection functions
that operate on the basis of undervoltage are blocked.
Figure 2-91 shows the effect on the protection functions in case that a measuring voltage is detected by the
„fuse failure monitor“ „VT FuseFail“ (no. 170), „VT FuseFail>10s“ (no. 169), the additional measuring
voltage failure monitoring „Fail U absent“ (no. 168) and the binary input of the VT miniature circuit breaker
„>FAIL:Feeder VT“ (no. 361).
Figure 2-91 Effect of the measuring voltage failure

Table of Contents

Other manuals for Siemens SIPROTEC 7SD610

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SD610 and is the answer not in the manual?

Siemens SIPROTEC 7SD610 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SD610
CategoryRelays
LanguageEnglish

Related product manuals