181 Error: A/D converter (Error A/D-
conv.)
Device OUT on
off
* * LED BO 135 178 1 Yes
183 Error Board 1 (Error Board 1) Device OUT on
off
* * LED BO 135 171 1 Yes
184 Error Board 2 (Error Board 2) Device OUT on
off
* * LED BO 135 172 1 Yes
185 Error Board 3 (Error Board 3) Device OUT on
off
* * LED BO 135 173 1 Yes
186 Error Board 4 (Error Board 4) Device OUT on
off
* * LED BO 135 174 1 Yes
187 Error Board 5 (Error Board 5) Device OUT on
off
* * LED BO 135 175 1 Yes
188 Error Board 6 (Error Board 6) Device OUT on
off
* * LED BO 135 176 1 Yes
189 Error Board 7 (Error Board 7) Device OUT on
off
* * LED BO 135 177 1 Yes
190 Error Board 0 (Error Board 0) Device OUT on
off
* * LED BO 135 210 1 Yes
191 Error: Offset (Error Offset) Device OUT on
off
**LEDBO
192 Error:1A/5Ajumper different from
setting (Error1A/5Awrong)
Device OUT on
off
* * LED BO 135 169 1 Yes
193 Alarm: Analog input adjustment
invalid (Alarm adjustm.)
Device OUT on
off
* * LED BO 135 181 1 Yes
194 Error: Neutral CT different from
MLFB (Error neutralCT)
Device OUT on
off
* * LED BO 135 180 1 Yes
196 Fuse Fail Monitor is switched
OFF (Fuse Fail M.OFF)
Measurem.Superv OUT * * * LED BO 135 196 1 Yes
197 Measurement Supervision is
switched OFF (MeasSup OFF)
Measurem.Superv OUT on
off
* * LED BO 135 197 1 Yes
234.2100 U<, U> blocked via operation
(U<, U> blk)
Voltage Prot. IntSP on
off
**LEDBO
285 Power factor alarm (cosϕ alarm) Set Points(MV) OUT on
off
**LEDBO
289 Alarm: Current summation super-
vision (Failure Σi)
Measurem.Superv OUT on
off
* * LED BO 135 250 1 Yes
290 Alarm: Broken current-wire de-
tected L1 (Broken Iwire L1)
Measurem.Superv OUT on
off
* * LED BO 135 137 1 Yes
291 Alarm: Broken current-wire de-
tected L2 (Broken Iwire L2)
Measurem.Superv OUT on
off
* * LED BO 135 138 1 Yes
292 Alarm: Broken current-wire de-
tected L3 (Broken Iwire L3)
Measurem.Superv OUT on
off
* * LED BO 135 139 1 Yes
295 Broken wire supervision is
switched OFF (Broken wire OFF)
Measurem.Superv OUT * * * LED BO
296 Current summation superv is
switched OFF (Σi superv. OFF)
Measurem.Superv OUT * * * LED BO
297 Broken current-wire at other end
L1 (ext.Brk.Wire L1)
Measurem.Superv OUT on
off
**LEDBO
298 Broken current-wire at other end
L2 (ext.Brk.Wire L2)
Measurem.Superv OUT on
off
**LEDBO
299 Broken current-wire at other end
L3 (ext.Brk.Wire L3)
Measurem.Superv OUT on
off
**LEDBO
301 Power System fault
(Pow.Sys.Flt.)
P.System Data 2 OUT ON
OFF
ON * 135 231 2 Yes
302 Fault Event (Fault Event) P.System Data 2 OUT * ON * 135 232 2 No
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation