Appendix
A.8 Information List
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
415
5212 Frequency protection is
BLOCKED (Freq. BLOCKED)
Frequency Prot. OUT on
off
on off * LED BO 70 182 1 Yes
5213 Frequency protection is ACTIVE
(Freq. ACTIVE)
Frequency Prot. OUT on
off
* * LED BO 70 183 1 Yes
5215 Frequency protection undervolt-
age Blk (Freq UnderV Blk)
Frequency Prot. OUT on
off
on off * LED BO 70 238 1 Yes
5232 Frequency protection: f1 picked
up (f1 picked up)
Frequency Prot. OUT * on off * LED BO 70 230 2 Yes
5233 Frequency protection: f2 picked
up (f2 picked up)
Frequency Prot. OUT * on off * LED BO 70 231 2 Yes
5234 Frequency protection: f3 picked
up (f3 picked up)
Frequency Prot. OUT * on off * LED BO 70 232 2 Yes
5235 Frequency protection: f4 picked
up (f4 picked up)
Frequency Prot. OUT * on off * LED BO 70 233 2 Yes
5236 Frequency protection: f1 TRIP (f1
TRIP)
Frequency Prot. OUT * on * LED BO 70 234 2 Yes
5237 Frequency protection: f2 TRIP (f2
TRIP)
Frequency Prot. OUT * on * LED BO 70 235 2 Yes
5238 Frequency protection: f3 TRIP (f3
TRIP)
Frequency Prot. OUT * on * LED BO 70 236 2 Yes
5239 Frequency protection: f4 TRIP (f4
TRIP)
Frequency Prot. OUT * on * LED BO 70 237 2 Yes
5240 Frequency protection: TimeOut
Stage f1 (Time Out f1)
Frequency Prot. OUT * * * LED BO
5241 Frequency protection: TimeOut
Stage f2 (Time Out f2)
Frequency Prot. OUT * * * LED BO
5242 Frequency protection: TimeOut
Stage f3 (Time Out f3)
Frequency Prot. OUT * * * LED BO
5243 Frequency protection: TimeOut
Stage f4 (Time Out f4)
Frequency Prot. OUT * * * LED BO
5803 >BLOCK restricted earth fault
prot. (>BLOCK REF)
REF SP * * * LED BI BO
5811 Restricted earth fault is switched
OFF (REF OFF)
REF OUT on
off
**LEDBO76111Yes
5812 Restricted earth fault is
BLOCKED (REF BLOCKED)
REF OUT on
off
on off * LED BO 76 12 1 Yes
5813 Restricted earth fault is ACTIVE
(REF ACTIVE)
REF OUT on
off
**LEDBO76131Yes
5816 Restr. earth flt.: Time delay
started (REF T start)
REF OUT * on off * LED BO 76 16 2 Yes
5817 Restr. earth flt.: picked up (REF
picked up)
REF OUT * on off m LED BO 76 17 2 Yes
5821 Restr. earth flt.: TRIP (REF TRIP) REF OUT * on m LED BO 76 21 2 No
5826 REF: Value D at trip (without
Tdelay) (REF D:)
REF VI * on off 76 26 4 No
5827 REF: Value S at trip (without
Tdelay) (REF S:)
REF VI * on off 76 27 4 No
6854 >Trip circuit superv. 1: Trip Relay
(>TripC1 TripRel)
TripCirc.Superv SP on
off
**LEDBIBO
6855 >Trip circuit superv. 1: Breaker
Relay (>TripC1 Bkr.Rel)
TripCirc.Superv SP on
off
**LEDBIBO
6856 >Trip circuit superv. 2: Trip Relay
(>TripC2 TripRel)
TripCirc.Superv SP on
off
**LEDBIBO
6857 >Trip circuit superv. 2: Breaker
Relay (>TripC2 Bkr.Rel)
TripCirc.Superv SP on
off
**LEDBIBO
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation