EasyManua.ls Logo

Siemens SIPROTEC 7SD610 - Page 416

Siemens SIPROTEC 7SD610
448 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
A.8 Information List
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
416
6858 >Trip circuit superv. 3: Trip Relay
(>TripC3 TripRel)
TripCirc.Superv SP on
off
**LEDBIBO
6859 >Trip circuit superv. 3: Breaker
Relay (>TripC3 Bkr.Rel)
TripCirc.Superv SP on
off
**LEDBIBO
6861 Trip circuit supervision OFF
(TripC OFF)
TripCirc.Superv OUT on
off
* * LED BO 170 53 1 Yes
6865 Failure Trip Circuit (FAIL: Trip cir.) TripCirc.Superv OUT on
off
* * LED BO 192 36 1 Yes
6866 TripC1 blocked: Binary input is
not set (TripC1 ProgFAIL)
TripCirc.Superv OUT on
off
**LEDBO
6867 TripC2 blocked: Binary input is
not set (TripC2 ProgFAIL)
TripCirc.Superv OUT on
off
**LEDBO
6868 TripC3 blocked: Binary input is
not set (TripC3 ProgFAIL)
TripCirc.Superv OUT on
off
**LEDBO
7104 >BLOCK Backup OverCurrent
I>> (>BLOCK O/C I>>)
Back-Up O/C SP on
off
**LEDBIBO6441Yes
7105 >BLOCK Backup OverCurrent I>
(>BLOCK O/C I>)
Back-Up O/C SP on
off
**LEDBIBO6451Yes
7106 >BLOCK Backup OverCurrent Ip
(>BLOCK O/C Ip)
Back-Up O/C SP on
off
**LEDBIBO6461Yes
7107 >BLOCK Backup OverCurrent
Ie>> (>BLOCK O/C Ie>>)
Back-Up O/C SP on
off
**LEDBIBO6471Yes
7108 >BLOCK Backup OverCurrent
Ie> (>BLOCK O/C Ie>)
Back-Up O/C SP on
off
**LEDBIBO6481Yes
7109 >BLOCK Backup OverCurrent
Iep (>BLOCK O/C Iep)
Back-Up O/C SP on
off
**LEDBIBO6491Yes
7110 >Backup OverCurrent Instanta-
neousTrip (>O/C InstTRIP)
Back-Up O/C SP on
off
on off * LED BI BO 64 10 1 Yes
7111 >BLOCK direct. Backup Over-
Current I> (>BLOCK Dir. I>)
Back-Up O/C SP on
off
**LEDBIBO64111Yes
7112 >BLOCK direct. Backup Over-
Current Ip (>BLOCK Dir. Ip)
Back-Up O/C SP on
off
**LEDBIBO64121Yes
7113 >BLOCK direct. Backup Over-
Current Ie> (>BLOCK Dir. Ie>)
Back-Up O/C SP on
off
**LEDBIBO64131Yes
7114 >BLOCK direct. Backup Over-
Current Iep (>BLOCK Dir. Iep)
Back-Up O/C SP on
off
**LEDBIBO64141Yes
7130 >BLOCK I-STUB (>BLOCK I-
STUB)
Back-Up O/C SP on
off
**LEDBIBO64301Yes
7131 >Enable I-STUB-Bus function (>I-
STUB ENABLE)
Back-Up O/C SP on
off
on off * LED BI BO 64 31 1 Yes
7132 >BLOCK Backup OverCurrent
Ie>>> (>BLOCK O/CIe>>>)
Back-Up O/C SP on
off
**LEDBIBO64321Yes
7151 Backup O/C is switched OFF
(O/C OFF)
Back-Up O/C OUT on
off
**LEDBO64511Yes
7152 Backup O/C is BLOCKED (O/C
BLOCK)
Back-Up O/C OUT on
off
on off * LED BO 64 52 1 Yes
7153 Backup O/C is ACTIVE (O/C
ACTIVE)
Back-Up O/C OUT * * * LED BO 64 53 1 Yes
7161 Backup O/C PICKED UP (O/C
PICKUP)
Back-Up O/C OUT * off m LED BO 64 61 2 Yes
7162 Backup O/C PICKUP L1 (O/C
Pickup L1)
Back-Up O/C OUT * on * LED BO 64 62 2 Yes
7163 Backup O/C PICKUP L2 (O/C
Pickup L2)
Back-Up O/C OUT * on * LED BO 64 63 2 Yes
7164 Backup O/C PICKUP L3 (O/C
Pickup L3)
Back-Up O/C OUT * on * LED BO 64 64 2 Yes
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation

Table of Contents

Other manuals for Siemens SIPROTEC 7SD610

Related product manuals