EasyManua.ls Logo

Siemens SIPROTEC 7SD610 - Page 84

Siemens SIPROTEC 7SD610
448 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
2.5 Restricted Earth Fault Protection (optional)
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
84
Evaluation of Measurement Quantities
The earth fault differential protection compares the fundamental component of the current flowing in the star-
point connection, which is designated as 3I
0
' in the following, with the fundamental component of the sum of
the phase currents designated in the following as 3I
0
”. Thus, the following applies (Figure 2-29):
3I
0
' = I
SP
3I
0
" = I
L1
+ I
L2
+ I
L3
Only 3I
0
' acts as the tripping effect quantity. During a fault within the protected zone this current is always
present.
Figure 2-29 Principle of restricted earth fault protection
When an earth fault occurs outside the protected zone, a zero sequence current also flows though the phase
current transformers. This is, on the primary side, in counter-phase with the starpoint current and has equal
magnitude. Therefore, both the magnitude of the currents and their phase relationship are evaluated for re-
straint purposes. The following is defined:
A tripping current
I
Ref
=|3I
0
'|
and a stabilisation or restraining current
I
Rest
= k · ( |3I
0
'–3I
0
"| |3I
0
'+3I
0
"| )
where k is a stabilisation factor which will be explained below, at first we assume k = 1. I
REF
produces the trip-
ping effect quantity, I
Rest
counteracts this effect.
To illustrate the effect, have a look at the three important operating conditions with ideal and adapted measured
values:

Table of Contents

Other manuals for Siemens SIPROTEC 7SD610

Related product manuals