Pre-assembled load feeders
In the 3RA2 fuseless load feeder, the 3RV2 motor starter protector takes on the dual function of
overload protection and short-circuit protection. Upstream protective devices such as melting
fuses or limiters are super󹪞uous, as the load feeder is capable of withstanding short circuits up
to 150 kA at 400 V.
The 3RT2 contactor is suitable for extremely complex switching tasks requiring maximum
endurance.
The trip class on all pre-assembled 3RA2 feeders is CLASS 10.
Self-assembled load feeders
Thanks to the 󹪞exible SIRIUS modular system, load feeders can be assembled for the most
diverse requirements.
These load feeders can be fuseless or fused. Load feeders for starting motors can be assembled
for the following startup types, for example:
Direct-on-line start
Reversing start
Star-delta (wye-delta) start
Soft start
Con󹪝guration with solid-state switching devices for high switching frequencies
In the case of a con󹪝guration with overload relay, a tripping class up to CLASS 30 can be set. In
the case of a con󹪝guration with SIMOCODE, a tripping class up to CLASS 40 can be set.
Reference
More information ... Can be found ...
About the functions of motor starter protectors In the "References" appendix under "Manuals - SIR‐
IUS Modular System (Page 138)" in the "SIRIUS -
SIRIUS 3RV motor starter protectors" manual.
SIRIUS 3RA Load Feeders
Equipment Manual, 02/2022, A5E03656507520A/RS-AC/004 25