Commissioning 
  13.4 Setting the motor protection function 
SIRIUS 3RW30 / 3RW40 
Manual, 10/2018, NEB535199502000/RS-AB/005 
119 
 
Setting the motor protection function 
The motor overload protection function is implemented on the basis of the winding 
temperature. This indicates whether the motor is overloaded or functioning in the normal 
operating range. 
The winding temperature can either be calculated with the help of the integrated, electronic 
motor overload function or measured with a connected motor thermistor. 
 
Setting the electronic motor overload protection 
 
 
 
The rated operational current of the motor must be set with the I
e
 potentiometer according to 
the mains voltage and the motor connection (wye-delta).  
The current flow during motor operation is measured by measuring the current with 
transformers integrated in the soft starter. This value is also used for the current limiting 
function. The temperature rise in the winding is calculated based on the rated operational 
current set for the motor. 
You can set the required trip class (10, 15, or 20) with the CLASS potentiometer. A trip is 
generated by the soft starter when the standardized characteristic is reached, depending on 
the trip class (CLASS setting).  
The trip class specifies the maximum time within which a protective device must trip from a 
cold state at 7.2 x the rated operational current (motor protection to IEC 60947). The tripping 
characteristics represent this time as a function of the tripping current (refer to chapter Motor 
protection tripping characteristics for 3RW40 (with symmetry) (Page 157)).