Functions
5.4 Functions of the RESET buttons
SIRIUS 3RW30 / 3RW40
48 Manual, 10/2018, NEB535199502000/RS-AB/005
5.4.1.2
Manual RESET
Manual RESET via RESET/TEST button (LED RESET MODE off)
You can reset a fault by pressing the RESET/TEST button.
5.4.1.3
Remote RESET
Remote RESET (LED RESET MODE green)
You can reset a pending error message by removing the control feed voltage for more than
1.5 s.
5.4.1.4
Auto RESET
Auto RESET (LED RESET MODE yellow)
If you set the RESET mode to AUTO, a fault is automatically reset.
If the motor overload protection function trips: after 5 minutes
On tripping the intrinsic device protection:
- after 30 seconds upon overload of the thyristors,
- after 60 seconds upon overload of the bypasses
If the thermistor evaluation function trips: after the temperature sensor in the motor has
cooled down
WARNING
Automatic restart
Danger of death, serious injury, or property damage.
The automatic reset mode (AUTO RESET) must not be used in applications where there
is a risk of serious injury to persons or substantial damage to property if the motor starts
up again unexpectedly. The start command (e.g. issued by a contact or the PLC) must
be reset prior to issuing a RESET command because the motor attempts to restart
again automatically following this RESET command if a start command is still present.
This particularly applies if the motor protection has tripped. For safety reasons, you are
advised to integrate the group fault output (terminals 95 and 96) in the controller.