Commissioning
13.7 Functions of the outputs
SIRIUS 3RW30 / 3RW40
124 Manual, 10/2018, NEB535199502000/RS-AB/005
Reparameterizing the ON / RUN output
A: Control voltage is present and the soft starter is in the normal, fault-free position:
The DEVICE LED is continuously lit (green) while the STATE / BYPASSED and FAILURE
LEDs are off.
The AUTO LED indicates the color of the set RESET mode.
B: Start programming:
(On the 3RW402 device, remove the RESET MODE cover as shown in chapter Setting the
RESET MODE (Page 47).) Press the RESET MODE button (2) for longer than 2 s until the
DEVICE LED (3) flickers (green). Hold the RESET MODE button (2) pressed down.
C: Simultaneously press the RESET/TEST button (1) for longer than 1 s until the DEVICE
LED (3) lights up (red). The active mode set at the ON / RUN output is indicated by the
STATE / BYPASSED / FAILURE LED (4):
STATE / BYPASSED / FAILURE LED (4) flashes (green): ON mode (factory setting).
STATE / BYPASSED / FAILURE LED (4) flickers (green): RUN mode.
D: Change the mode:
Press the RESET MODE button (2) briefly. By pressing this button, you change the mode at
the output, and the new mode is indicated by the STATE / BYPASSED / FAILURE LED (4):
STATE / BYPASSED / FAILURE LED (4) flickers (green): RUN mode is set.
STATE / BYPASSED / FAILURE LED (4) flashes (green): ON mode is set.