Loading...
The bolts must be tightened using up to 50% of the max. tightening torque for the pipe
dimensions stated. The max. tightening torque for different size pipes is given in the table.
The bolts must now be cross-tightened in the sequence shown, using up to 100% torque.
DN M
A
[N
m
]
2 13
3 13
6 13
10 13
15 16
25 30
40 54
50 90
65 90
80 90
100 115
10 Nm - 1 kpm
NOTICE
Do not use sharp objects to remove the blanks as this can damage the liner!
Installing/Mounting
4.5 Mounting MAG 1100/1100 HT
SITRANS F M MAG 1100 sensor
26 Operating Instructions, 01/2018, A5E03433301-AC