Modbus RTU RS-485
15
SFIDK.PS.023.D2.02
Modbus Modbus No. of Data Read/
register address bytes type
Description
write
4:00601 600 2 Byte
Slave ID:
0x2A = Siemens R
4:00602 601 2 Byte
Run indicator:
0x00 = not running R
0xFF = running
4:00603 602 2 Byte
Product code:
24 = MAG 6000 R
25 = MASS 6000
4:00604 603 3 Byte array Capability bits R
4:00606 605 2 Word
Flowmeter revision:
e.g. 0x0201 = v2.01
R
4:00607 606 2 Word
Modbus revision:
e.g. 0x0201 = v2.01
R
4:00608 607 12 String Manufacturer name R
4:00614 613 18 String Product name R
4:00623 622 12 String Modbus module name R
Slave ID
6. Modbus holding registers
Modbus Modbus No. of Data Read/
register address bytes type
Description
write
4:00641 640 18 String TAG R/W
TAG
Modbus Modbus No. of Data Read/
register address bytes type
Description
write
4:00650 649 20 String
Modbus module SW version:
R
e.g. „1.00“
4:00660 659 2 Byte
Modbus module HW version:
e.g. „2“
R
Modbus module version
Modbus Modbus No. of Data Read/
register address bytes type
Description
write
4:00681 680 2 word Last Coil Error (CoilAddr)
(Modbus cmd: 1 or 5)
R
4:00682 681 2 word Last Coil Error (ErrorNo)
(See appendix E)
R
4:00683 682 2 word Last HoldReg Error
(HoldReg Addr) R
(Modbus cmd: 3 or 16)
4:00684 683 2 word Last HoldReg Error (ErrorNo)
(See appendix E)
R
Modbus error reporting
6.3 Modbus application
settings