Modbus RTU RS-485
16
SFIDK.PS.023.D2.02
Modbus Modbus No. of Data Read/
register address bytes type
Description
write
4:02001 2000 2 Byte
Flow direction:
0 = Negative R/W
1 = Positive
4:02002 2001 4 Float Massflow max. (kg/s) R/W
4:02004 2003 4 Float Volumeflow max. (m
3
/s) R/W
4:02010 2009 4 Float Density min. (kg/m
3
) R/W
4:02012 2011 4 Float Density max. (kg/m
3
) R/W
4:02014 2013 4 Float Sensor temperature min. (°C) R/W
4:02016 2015 4 Float Sensor temperature max. (°C) R/W
4:02018 2017 4 Float Fraction A max. (kg/s) R/W
4:02020 2019 4 Float Fraction B max. (kg/s) R/W
4:02022 2021 4 Float % fraction A min. (1/100 %)
e.g. value 0.05 = 5 %
R/W
4:02024 2023 4 Float % fraction A max. (1/100 %)
e.g. value 0.8 = 80 %
R/W
4:02026 2025 4 Float
Low flow cut off:
(1/100 %)
e.g. value = 0,02 = 2 %
R/W
4:02028 2027 4 Float Empty pipe limit (kg/m
3
) R/W
4:02030 2029 2 Byte
Empty pipe on/off:
0 = Off R/W
1 = On
4:02031 2030 2 Byte
Noise filter:
1 = min.
2
3
R/W
4
5 = max.
4:02032 2031 2 Byte
Error level:
1 = Warning
2 = Permanent
R/W
3 = Fatal
4:02033 2032 2 Byte
Zero adjust mode:
0 = Auto R/W
1 = Manual
4:02034 2033 4 Float Manual zero adjust (kg/s) R/W
4:02036 2035 2 Word Zero adjust time (s) R/W
4:02037 2036 4 Float Zero sigma (kg/s) R
4:02039 2038 4 Float Zero sigma limit (kg/s) R/W
MASS 6000
6. Modbus holding registers
Modbus Modbus No. of Data Read/
register address bytes type
Description
write
4:02001 2000 2 Byte
Flow direction:
0 = Negative R/W
1 = Positive
4:02006 2005 4 Float Q max. (m
3
/s) R/W
4:02008 2007 4 Float Q max. 2 (Night) (m
3
/s) R/W
4:02026 2025 4 Float
Low flow cut off:
e.g. value 0,02 = 2 %
R/W
4:02030 2029 2 Byte
Empty pipe on/off:
0 = Off R/W
1 = On
4:02032 2031 2 Byte
Error level:
1 = Warning
2 = Permanent
R/W
3 = Fatal
4:02033 2032 2 Byte
Zero adjust mode
1)
:
0 = Auto R/W
1 = Manual
4:02034 2033 4 Float Manual zero adjust
1)
(ms/s) R/W
4:02041 2040 2 Byte
Mains Frequency
0 = 50 Hz R/W
1 = 60 Hz
MAG 6000
6.4 Basic settings
1)
Only available in MAG 6000 SV