Modbus RTU RS-485
17
SFIDK.PS.023.D2.02
Modbus Modbus No. of Data Read/
register address bytes type
Description
write
4:02101 2100 2 Byte
Totalizer 1 selection:
1 = Massflow
2 = Fraction A R/W
3 = Fraction B
4 = Volumeflow
4:02102 2101 2 Byte
Totalizer 1 direction:
0 = Reverse
1 = Forward
R/W
2 = Net
4:02103 2102 2 Byte
Totalizer 2 selection:
1 = Massflow
2 = Fraction A R/W
3 = Fraction B
4 = Volumeflow
4:02104 2103 2 Byte
Totalizer 2 direction:
0 = Reverse
1 = Forward
R/W
2 = Net
MASS 6000
6. Modbus holding registers
Modbus Modbus No. of Data Read/
register address bytes type
Description
write
4:02102 2101 2 Byte
Totalizer 1 direction:
0 = Reverse
1 = Forward
R/W
2 = Net
4:02104 2103 2 Byte
Totalizer 2 direction:
0 = Reverse
1 = Forward
R/W
2 = Net
MAG 6000
Modbus Modbus No. of Data Read/
register address bytes type
Description
write
4:02201 2200 2 Byte
Current Output 1 selection:
0 = Off R/W
1 = On
4:02202 2201 2 Byte
Current Output 1 direction:
1 = Unidirectional R/W
2 = Bidirectional
4:02203 2202 2 Byte
Current Output 1 range:
0 = 0 - 20 mA
1 = 4 - 20 mA
R/W
2 = 4 - 20 mA + Alarm
4:02204 2203 4 Float Current Output 1 time constants R/W
4:02206 2205 2 Byte
Digital Output 1 function:
0 = Off
1 = Pulse
2 = Frequency
R/W
3 = Error Level
4 = Error Number
5 = Direction/Limit
6 = Batch
4:02208 2207 2 Byte
Pulse 1 direction:
1 = Unidirectional R/W
2 = Bidirectional
MAG 6000
6.5 Totalizer
6.6 Output