Modbus RTU RS-485
25
SFIDK.PS.023.D2.02
Modbus Modbus No. of Data Read/
register address bytes type
Description
write
4:03201 3200 2 Word
System status:
bit0=RunIndicator
bit1=ErrorPendingOn
bit2=ErrPendChanged
bit3=Batching R
bit4=BatchPaused
bit5=Zeroadjusting
bit6=Totalizer1Hold
bit7=Totalizer2Hold
4:03202 3201 2 Word Error pending 1* (oldest/first error)
0xFFFF = no error R
4:03203 3202 2 Word Error pending 2* R
4:03204 3203 2 Word Error pending 3* R
4:03205 3204 2 Word Error pending 4* R
4:03206 3205 2 Word Error pending 5* R
4:03207 3206 2 Word Error pending 6* R
4:03208 3207 2 Word Error pending 7* R
4:03209 3208 2 Word Error pending 8* R
4:03210 3209 2 Word Error pending 9* R
4:03211 3210 2 Byte
Batch status
0 = Idle
1 = Ready R
2 = Running
3 = Paused
Modbus Modbus No. of Data Read/
register address bytes type
Description
write
4:03212 3211 2 Byte
Zero adjust progress
0 = Idle
1 = Ready
R
2 = Running
Zero adjust progress MAG
6. Modbus holding registers
Modbus Modbus No. of Data Read/
register address bytes type
Description
write
4:03212 3211 4 Float Zero adjust progress (0-100 %) R
Zero adjust progress MASS
6.12 Flowmeter status
* Further information about the Error pending numbers can be found in the MAG/MASS 6000 manuals.