Modbus RTU RS-485
18
SFIDK.PS.023.D2.02
6. Modbus holding registers
Modbus Modbus No. of Data Read/
register address bytes type
Description
write
4:02209 2208 2 Byte
Pulse 1 width:
0 = 64 us
1 = 130 us
2 = 260 us
3 = 510 us
4 = 1.0 ms
5 = 2.0 ms
6 = 4.1 ms
7 = 8.2 ms
8 = 16 m R/W
9 = 33 ms
10 = 66 ms
11 = 130 ms
12 = 260 ms
13 = 520 ms
14 = 1.0 s
15 = 2.1 s
16 = 4.2 s
4:02212 2211 2 Byte Frequency 1 Direction
1 = Unidirectional R/W
2 = Bidirectional
4:02213 2212 2 Byte Frequency 1 Fmax.
0 = 10 kHz
1 = 5 kHz R/W
2 = 1 kHz
3 = 500 Hz
4:02214 2213 4 Float Frequency 1 Timeconstants R/W
4:02217 2216 2 Byte
Limit Digital mode:
0 = 1 setpoint
1 = 2 setpoints R/W
4:02218 2217 4 Float Limit Digital Setpoint min. (1/100%) R/W
4:02220 2219 4 Float Limit Digital Setpoint max. (1/100%) R/W
4:02222 2221 4 Float Limit Digital Hysteresis (1/100%) R/W
4:02224 2223 2 Byte
Relay Output 1 function:
0 = Off
3 = Error Level
4 = Error Number R/W
5 = Direction/Limit
6 = Batch
7 = Cleaning
4:02226 2225 2 Byte
Limit Relay mode:
0 = 1 setpoint R/W
1 = 2 setpoints
4:02227 2226 4 Float Limit Relay Setpoint min. (1/100%) R/W
4:02229 2228 4 Float Limit Relay Setpoint max. (1/100%) R/W
4:02231 2230 4 Float Limit Relay Hysteresis (1/100%) R/W
4:02233 2232 2 Byte Error number (0-255) R/W
4:02235 2234 4 Float Batch Quantity (m
3
) R/W
4:02237 2236 4 Float Batch Compensation (m
3
) R/W
4:02241 2240 2 Byte
Batch Time error on/off:
0 = Off R/W
1 = On
4:02242 2241 4 Dword Max. Batch time (s) R/W
4:02244 2243 2 Byte
Batch overrun on/off:
0 = Off R/W
1 = On
4:02245 2244 4 Float Batch overrun error (m
3
) R/W
4:02247 2246 2 Byte Batch counter up/down
0 = Down R/W
1 = Up
4:02248 2247 4 Float Batch Time constants R/W
4:02250 2249 4 Dword Batch cycle counter R
4:02291 2290 4 Float Volume per pulse (m
3
) R/W
4:02293 2292 2 Byte Pulse Polarity
0 = Negative R/W
1 = Positive
4:02294 2293 4 Float Pulse Timeout(s) R/W
MAG 6000
6.6 Output
(continued)