Manufacturer specific GSD file, in SIMATIC STEP 7 hardware configuration
Module possibillities
Modules are grouped into Process values, control commands, totalizers
and dosing.
Process values:
Mass flow, Density, Medium temperature, Volume flow, Standard volume
flow is updated in all devices.
Frame temperature is only updated if the device has a frame temperature
sensor built in Fractional flow A, B, %A and % B is only updated if the
device is ordered with fraction.
Totalizers:
Can either be selected as
total
(32 bit) or
total high res
(64 bit)
If a totalizer must be controlled, then the module
total set
or
total set high
res
must be selected.
Fraction A total, B total is only updated if the device is ordered with fraction.
Control commands:
Used for Zero point adjustment and other commands.
Dosing:
Can either be selected as Digital or Analog dosing module.
If a digital valve is controlled by the device directly, then the Digital module
must be selected.
If an analog valve is controlled by the device directly, then the Analog
module must be selected.
Detailed information for each module can be found in Modules for cyclic
data exchange, Manufacturer specific GSD.
Communication
2.9 Cyclic data exchange
FCT030 Profibus (From firmware 4.0)
Function Manual, 06/2018, A5E39931906-AB 23