Index Parameter name Data type
[size]
Access Annotation
47 UP‐
DATE_EVENT_MO
DE
Unsigned8 Read /
write
Holds the configuration for the behavior of the update event
flag in all status bytes
0: auto-acknowledge after 20 seconds.
1: manual acknowledge by means of parameter UP‐
DATE_EVENT_ACK
48 NE107_COMMON OctetString(6) Read only Detailed information of the device, bitwise coded. Allows set‐
ting of diagnostic flags specified by the NAMUR recommen‐
dation NE107 comprising common device diagnostics. The
device type specific diagnostics are allocated to the respec‐
tive transducer block (module/submodule) that characterizes
the device type mainly.
49 LINK_NE107_COM‐
MON
DS-69 Read /
write
Indicates / controls the reaction of the device on device spe‐
cific diagnostic events.
50 View_1 Read only Parameter to read the following block parameters at once:
· BLOCK_OBJECT
· OrderID
· SOFTWARE_REVISION
· HARDWARE_REVISION
· VendorID
· DeviceID
· IM_Serial_Number
· IM_Profile_ID
· IM_Profile_Specific_Type
51 View_2 Read /
write
Parameter to read the following block parameters at once:
· CURRENT_MODE
· DIAGNOSIS
· IM_Revision_Counter
· STARTUP_PARAM_VALIDITY
· BUS_ADDRESS
· IDENT_NUMBER
· BAUD_RATE
· WRITE_PROTECTION
· NE107_COMMON
52 View_3 Read /
write
Parameter to read and write the following block parameters
at once:
· IM_Tag_Function
· IM_Tag_Location
· IM_Descriptor
· LANGUAGE
· IM_Date
· IDENT_NUMBER_SELECTOR
Communication
2.10 Acyclic communication
FCT030 Profibus (From firmware 4.0)
30 Function Manual, 06/2018, A5E39931906-AB