Index Parameter name Data type
[size]
Access Annotation
40 IDENT_NUM‐
BER_SELECTOR
Unsigned8 Read only Specifies which ident number is used
0: PA profile 4 specific ident number
0 : PA profile 4 specific ident number
1 : Device specific ident number (81CB/81CC)
127: Automatic adaption (default)
128: MASS6000 (8127/8128)
129: PA profile 3 specific (9700, 1 AI)
130: PA profile 3 specific (9701, 2 AI)
131: PA profile 3 specific (9702, 3 AI)
132: PA profile 3 specific (9742, 3 AI, 1 TOT)
41 BUS_ADDRESS Unsigned8 Read /
write
PROFIBUS slave address that is currently set. Used by the
parameterization tool to create a complete snapshot of the
device parameterization.
42 IDENT_NUMBER Unsigned16 Read only Current ident number that is used by the cyclic master when
in cyclic data exchange. If the device is not in cyclic data ex‐
change the default manufacturer specific ident number is re‐
turned.
43 BAUD RATE Unsigned8 Read only Shows the current used baud rate.
0: 9.6 kbit/s
1: 19.2 kbit/s
2: 93.75 kbit/s
3: 187.5 kbit/s
4: 500 kbit/s
5: 1.5 Mbit/s
6: 3 Mbit/s
7: 6 Mbit/s
8: 12 Mbit/s
9: 31.25 kbit/s (MBP)
Note: The PA variant returns always code 9. The DP variant
does not support code 9 (31.25 kbit/s)
44 WRITE_PROTEC‐
TION
Unsigned16 Read only Information about active parameter protection.
Bit 2: Password write protection enabled
Bit 15: Custody transfer mode enabled
45 ALARM_DELAY Unsigned16 Read /
write
A coming event is suppressed until the suppression time has
elapsed. This prevents alarm flooding.
46 UP‐
DATE_EVENT_ACK
Unsigned8 Read /
write
Command to reset the update event flag in quality codes and
the DIAGNOSIS parameter in case that manual acknowledge
mode is enabled (UPDATE_EVENT_MODE)
Communication
2.10 Acyclic communication
FCT030 Profibus (From firmware 4.0)