Safety notes
2.3 Installation in hazardous area
SITRANS FCS200
Operating Instructions, 02/2011, A5E02508199-01
11
Table 2- 3 Sensor circuit
Sensor circuit (Terminal 5-6 and 7-8)
U
i
30 V DC
I
i
50 mA
P
i
0.4 W
C
i
Insignificant
L
i
14 mH
Uo 0.3 V AC
Temperature specifications for use in hazardous area
Table 2- 4 Temperature specifications
Temperature class Max. process temperature [°C] Ambient temperature [°C]
T4 125 -40 ... +60
T5 70 -40 ... +60
Special conditions for safe use
It is required that:
Electrical connections are in accordance with IEC/EN60079-14 (Installing Electrical
Systems in Explosion Hazardous Areas).
The protective cover over the power supply is properly installed. For intrinsically safe
circuits the connection area can be opened.
Appropriate cable connectors are used for the output circuits:
Intrinsically safe: blue
Non-intrinsically safe: black
Sensor and transmitter are connected to potential equalization.
For intrinsically safe output circuits potential equalization must be maintained along the
entire connection path.
When protective earth (PE) is connected, no potential difference between the protective
earth (PE) and the potential equalization (PA) can exist, even during a fault condition.