Maintenance and servicing
5.6 User data following replacement
SITRANS P DS III
36 Service Manual, 06/2014, A5E34219855-01
Status of user data following
replacement of application
electronics or measuring cell
Certificates and approvals / explosion
protection
①
-
* Polling address
①
-
* Min/max pointers for pressure / sensor
temperature
①
-
* Sensor calibration / zero calibration
①
-
* Sensor calibration / upper/lower calibration
①
-
* Position error calibration
①
0.0
* Operating hours counter, sensor
①
-
Operating unit / message
②
-
Operating unit / description
②
-
Device / software revision
②
-
Device / hardware revision
②
-
Device / field device revision
②
-
Device / date
②
-
Device / factory number
②
-
Display and user interface / local display unit
②
-
Display and user interface / bargraph
②
-
Display and user interface / local operation
②
-
Calibration interval for application electronics
(all settings)
②
-
Current saturation monitoring / alarm activation
②
-
Current saturation monitoring / saturation
alarm, alarm duration
②
-
* Operating hours counter, application
electronics
②
-
* Analog output D/A calibration (customer-
specific)
②
Like factory-set D/A calibration
* Min/max pointers for application electronics
temperature
②
-
Table 5- 2 SITRANS P DS III with PA