Maintenance and servicing
5.6 User data following replacement
SITRANS P DS III
Service Manual, 06/2014, A5E34219855-01
35
This chapter describes which user data is reset to the factory setting following replacement
of the application electronics or measuring cell.
The following tables are identified as follows:
*: The parameter names identified by * can be found in SIMATIC PDM under the menu items
"Device" or "View".
①: The user data identified by ① is reset to the factory setting following replacement of the
measuring cell.
②: The user data identified by ② is reset to the factory setting following replacement of the
application electronics.
Table 5- 1 SITRANS P DS III with HART
Status of user data following
replacement of application
electronics or measuring cell
Operating unit / TAG
①
-
Device / sensor serial number
①
-
Unit and cycle time / unit
①
bar
Unit and cycle time / cycle time
①
90 ms
Measuring limits / min. measuring range
①
-
Measuring limits / min. start-of-scale value,
max. full-scale value
①
-
Measured-value scaling, start-of-scale value
①
0.0
Measured-value scaling, full-scale value
①
Upper sensor limit
Analog output limits / lower/upper limit
①
3.8 / 20.5 mA
Alarm status / analog output alarm type
①
Lower
Alarm status / lower/upper alarm value
①
3.6 / 22.8 mA
Damping
①
0.1 s
Characteristic / transfer function
①
Linear
Characteristic / start of root extraction
①
5 %
Display and user interface / tracking unit
①
mA
Design (all material data)
①
-
Sensor calibration / upper/lower calibration
point
①
Like factory-set sensor limits, without
transformation
Sensor calibration / lower calibration point
①
0.0
Sensor calibration / upper calibration point
①
Upper sensor limit
Service interval for sensor (all settings)
①
-