This chapter describes the deviations from the technical specifications in the operating
instructions.
Deviations exist as follows in the measuring accuracy following replacement of the
application electronics or measuring cell:
Table 6- 1 Technical specifications > measuring accuracy
SITRANS P DS III with HART
No calibration of zero and span
Calibration of zero and span
Measurement deviation with
limit setting, including hysteresis
and repeatability
Linear characteristic curve
• r ≤ 10
Value doubled Value remains unchanged
Effect of ambient temperature
• At -10 … +60 °C (14 … 140
°F)
Value doubled Value doubled
r = maximum measuring span/set measuring span