Maintenance and servicing
5.7 Replacing parts
SITRANS P DS III
50 Service Manual, 06/2014, A5E34219855-01
4. Use a 2.5 mm Allen key to loosen the locking screw for fixing the measuring cell.
Damage to the ribbon cable
To avoid damage to the ribbon cable when installing or removing the measuring cell, do
not kink, pinch, tension or twist it.
• Do not kink, pinch, tension or twist the ribbon cable.
5. Turn the measuring cell counter-clockwise to remove it from the housing. To do this, use
a matching open-end wrench (relative pressure transmitter) or rotate the measuring cell
by hand.