6. Connect the input terminals .
,
,
&-&
2-wire, 3-wire or 4-wire RTD or
linear r
esistance
I1: Input 1
TC (internal CJC or
external 2-wire or 3-wire CJC)
,
6
Voltage input
(unipolar or bipolar)
3-wire or 4-wire potentiometer
7. Close the device.
Closing t
he device (Page 65)
5.9.3 Connecting the SITRANS TF420 dual chamber housing
Requirement
The device is opened. (Page 60)
If you use stranded wire used, you need a ferrule.
Note the maximum permissible core cross-section (Page 81).
Connecting
5.9 Connecting the SITRANS TF dual chamber housing
SITRANS TH100/TH100Slim/TH320/TH420/TR320/TR420/TF320/TF420
62 Compact Operating Instructions, 07/2021, A5E41865021-AE