Fault Possible cause/Remedy
Unrecognised hardware Unable to interface with the EEPROM
device on startup. Hardware error
- replace the PSU board
Software error
(includes – Checksum failure, Watchdog
Failure, S/W general error, Initialisation
failure)
Unlikely to occur. If observed report to
Poole Engineering (see section 1.2)
- Power cycle the Gemini3 unit if possible –
to attempt to remove the fault
Table 10 – PSU board fault troubleshooting
4.6.3 Pinouts
PSU Inputs and Outputs – 15 Way 3.5mm pitch
Pin Function
Card/
Port
Bit
ID
Loom Colours
667/1/30607/000
15 Input 8
Gspi15.in.0
8 Brown/Green
14 Input 7 7 Pink
13 Input 6
6 Grey
12 Input 5
5 Orange
11 Input 4
4 Violet
10 Input 3
3 Brown
9 Input 2
2 Yellow
8 Input 1
1 Blue
7
0V
Common
-
- White
6 N.C. O/P 2
Gspi15.out.1
2 Orange/Grey
5 Com O/P 2
2 Blue/White
4 N.O. O/P 2 2 Blue/Orange
3 N.C. O/P 1
1 White/Orange
2 Com O/P 1 1 Red/White
1 N.O. O/P 1
1 Red/Orange
Table 11 – PSU Inputs and Outputs - 15 Way 3.5mm pitch