EasyManua.ls Logo

Siemens WL Series - Metering Voltage Details

Siemens WL Series
83 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WL Circuit Breaker selection and application guide
54
VT / PT connections for the WL Breaker when equipped
with metering
WL power metering (“Meter Function”) can accept 3W or 4W
(LL/LN) system voltage connections.
The trip unit settings available are:
1) VT Primary Voltage (240V, 480V, 600V)
2) VT Secondary Voltage (100V, 110V, 120V)
3) VT Connection (Wye / LN, Delta / LL)
Three VTs must be used at all times.
All three VTs should be rated for the nominal system L-L voltage
(e.g. 480V) and may have either 100V, 110V or 120V secondary
voltages.
The following ratios are suggested and equivalent VTs can
be used:
240:120 = 2:1 (ITI Part # 460-240 or 468-240)
480:120 = 4:1 (ITI Part # 460-480 or 468-480)
600:120 = 5:1 (ITI Part # 460-600 or 468-600)
VT Accuracy:
Each Metering Module presents a purely resistive (unity power
factor) load to the transformer. Assuming no other devices
connected to the VT, a ITI type 486 VT can safely feed 10
metering modules and and still maintain 0.6% accuracy
assuming the wiring from the VT to the individual metering
modules is twisted pair and kept to a minimum length.
Metering VT settings:
Delta/Wye: Delta
VT Primary: 480 (for example)
VT Secondary: 120 (for example)le)
Metering VT settings:
Delta/Wye: Wye
VT Primary: 480 (for example)
VT Secondary: 120 (for example)
Low Voltage Breaker
Metering voltage details

Table of Contents

Other manuals for Siemens WL Series

Related product manuals