Page 12
Document No: 4020-M010 1st February, 1997 Issue 2.0
Alarm mode shows the alarm details. For example:
Zn6 Level 4 East V-Smoke
Ackd Alarm # 1 of 3 11:27:00
- The top line shows the zone number, a description of the location, and the type
of device on the circuit.
- The bottom line shows the status of the alarm at that time, the number of the
displayed alarm and the total number of alarms, and the time the alarm was
activated.
The status of the alarm may be "Alarm" or "Normal". Detectors once activated will
remain in the "Alarm" state but devices such as flow switches may indicate "Normal"
when they are not actually operating.
Fault mode shows the fault details. For example:
Zn8 Level 5 West V-Smoke
Ackd Fault # 2 of 2 14:38:00
- The top line shows the Zone Number and the fault location description. For
output control circuit faults it would also show "On" or "Off" on the right,
indicating the state of the relay before the fault.
- The bottom line shows the status of the fault at that time, the number of the
displayed fault and the total number of faults, and the time the fault occurred.
Isolated mode shows the details of isolated circuits or zones. For example:
Zn4 Level 7 Board Room V-Smoke
Isol Ackd Alarm # 1 of 2 12:27:00
- The top line shows the Zone Number for input circuits or the Control Point
number for output circuits, the location description, and, for output circuits, the
status of the circuit before being isolated.
- The bottom line shows the status of the circuit/zone at that time, the number of
the displayed isolated circuit/zone, the total number of isolated circuits/zones,
and the time the circuit/zone was isolated.

Other manuals for Simplex 4020

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4020 and is the answer not in the manual?

Simplex 4020 Specifications

General IconGeneral
TypeFire Alarm Control Panel
ManufacturerSimplex
Model4020
DisplayLCD
Frequency50/60 Hz
Battery BackupYes
NAC Outputs4
Power120/240 VAC
Voltage120/240 VAC
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity RangeUp to 93% RH, non-condensing
Communication ProtocolOptional