Page 16 
 
 
 
 
 
 
Document No: 4020-M010  1st February, 1997  Issue 2.0 
 
 
 
6.2 RESETTING ZONES IN ALARM 
 
After the zones have been checked, the fire extinguished, or the problem rectified, the 
area is secure and the system needs to be reset. 
 
To put the panel back on line press the RESET button which sends 
a reset signal to the zones in the alarm list. If all the zone circuits 
are operating correctly the system resets. 
 
It takes ten seconds for the reset to take place. During the reset period, the alarm light 
will be extinguished, and the following message will be displayed: 
 
 
  *** DETECTOR RESET IN PROGRESS ***    
         Alarms: 00 Faults: 00 Isolated: 00 
 
If a zone does not reset after the ten second reset period it means that the  zone is still 
in alarm and the panel is still putting a call through to the Brigade. 
 
What is now needed is to isolate the zones that are still in alarm. 
 
6.3 ISOLATING ZONES IN ALARM 
 
To isolate zones that are still in alarm, press the ISOLATE button. This will have the 
following effect: 
 
 
Isolates all circuits that are still in alarm with one press of the key  
 
 
Resets the Brigade call and the ancillary control functions (ACF) light.   
Only  the  zones  in  alarm  are  isolated.    The  rest  of  the  building  is  still 
protected. 
 
An isolated indication (Isol) comes up in the display on the left of the bottom line. 
 
After isolating non-resetting zones, press the BRIGADE TEST button to test the alarm 
call circuit to the fire Brigade. 
 
 
CAUTION
 
 
Before leaving the panel, ensure that the panel door is closed and locked.  If this 
is not done and a fire occurs the Brigade will be called but the ancillary controls 
will not shut down and the fire alarm  bell connected to the panel will not ring. 
RESET 
 
ISOLATE