Page 38 
 
 
 
 
 
 
Document No: 4020-M010  1st February, 1997  Issue 2.0 
   
 
9 PLACING INTO OPERATION 
 
To place a correctly installed 4020 FIP into operation perform the following steps: 
 
STEP 1  Ensure  that  the  mains  isolate  switch  is  OFF  and  batteries  are 
disconnected. 
 
STEP 2  Ensure  that 240V AC  supply  is connected to the panel  from  the mains 
distribution board. 
 
STEP 3  Turn  the  panel  mains  isolate  switch  ON  .  The  panel  sounder  will  start  
beeping and the Fault LED will be flashing and the following POWER-UP 
message will be displayed: 
 
 
 ** WARNING - CPU RESET HAS OCCURRED ** 
     PRESS ANY KEY TO SILENCE SOUNDER 
 
Press  the  ACKNOWLEDGE  key  to  silence  the  sounder  and  check  the 
status of the following: 
 
-  PWR ON LED indicator is illuminated. 
-  BELL ISOLATED indicator is illuminated. 
-  ACF ISOLATED indicator is illuminated. 
-  Display is in normal display mode ie: 
 
 
 SIMPLEX AUSTRALIA - Time of day - Bat: OK  
 Alarms: 00 Faults: 00     Isolated : 00   
 
STEP 4  Next the fault sounder will start beeping to indicate a battery fault. Press 
the  ACKNOWLEDGE  key  to  silence  the  buzzer  and  acknowledge  the 
fault. 
Now adjust the battery charger float voltage as per section 9.1 
 
STEP 5  Perform a lamp test by pressing the LAMP TEST key. 
 
STEP 6  Perform an alarm test by pressing the ALARM(ALM) TEST key. 
Acknowledge  each  alarm  and  then  press  the  RESET  key  to  reset  the 
alarm zone circuits. 
 
 
 
 
 
 
 
 
 
 
ALM 
TEST 
 
4 
ACK+
 
 
 
5 
RST