EasyManua.ls Logo

Simplex 4020 - Placing into Operation

Simplex 4020
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 38
Document No: 4020-M010 1st February, 1997 Issue 2.0
9 PLACING INTO OPERATION
To place a correctly installed 4020 FIP into operation perform the following steps:
STEP 1 Ensure that the mains isolate switch is OFF and batteries are
disconnected.
STEP 2 Ensure that 240V AC supply is connected to the panel from the mains
distribution board.
STEP 3 Turn the panel mains isolate switch ON . The panel sounder will start
beeping and the Fault LED will be flashing and the following POWER-UP
message will be displayed:
** WARNING - CPU RESET HAS OCCURRED **
PRESS ANY KEY TO SILENCE SOUNDER
Press the ACKNOWLEDGE key to silence the sounder and check the
status of the following:
- PWR ON LED indicator is illuminated.
- BELL ISOLATED indicator is illuminated.
- ACF ISOLATED indicator is illuminated.
- Display is in normal display mode ie:
SIMPLEX AUSTRALIA - Time of day - Bat: OK
Alarms: 00 Faults: 00 Isolated : 00
STEP 4 Next the fault sounder will start beeping to indicate a battery fault. Press
the ACKNOWLEDGE key to silence the buzzer and acknowledge the
fault.
Now adjust the battery charger float voltage as per section 9.1
STEP 5 Perform a lamp test by pressing the LAMP TEST key.
STEP 6 Perform an alarm test by pressing the ALARM(ALM) TEST key.
Acknowledge each alarm and then press the RESET key to reset the
alarm zone circuits.
ALM
TEST
4
ACK+
5
RST

Other manuals for Simplex 4020

Related product manuals