4020 OPERATORS MANUAL Page 37
Document No: 4020-M010 1st February, 1997 Issue 2.0
NOTES: 1 You can press KEY 5 (RST) key to abort the walk test at any time
before the test timeout expires.
2 All results of the Walk test are stored in the Alarm log and logged to
a Serial Printer if connected. The Alarm Log can have up to 99
entries.
3 The Detector reset time is set to 10 seconds and Alarm Verification
is bypassed.
4 When a zone is put into alarm during Walktest, any associated
ACF circuits will not operate.
5 The Brigade alarm output will not operate during Walktest Mode.
Hence the panel is effectively disconnected from the Brigade
during Walktest mode. Therefore ensure you press KEY 5 (RST)
key to abort the walk test at any time before the test timeout
expires.