Page 44 
 
 
 
 
 
 
Document No: 4020-M010  1st February, 1997  Issue 2.0 
 
10 APPENDIX  
10.1 Alarm Verification Zone Processing 
 
Alarm verification  (AVF) is a technique to minimise false alarms on detector circuits 
and operates as follows: 
 
When a  zone  is  detected  as  being  in an alarm  condition,  the alarm condition is not 
immediately processed. Rather the zone in alarm is  reset  for a period of 12 seconds 
afterwhich it is then checked for an alarm condition. If the detector is still in alarm after 
the  12  second  alarm  verification  period  then  the  alarm  is  processed  as  an  alarm 
condition and will  operate programmed output functions. 
 
If the zone is not in alarm after the 12 sec period, a timing window is activated for a 
period of 150 seconds. Any alarms registered during this 150 second window will be 
processed as an alarm condition and will operate programmed output functions. If no 
alarm conditions are detected at the end of the 150 second window then the alarm zone 
processing reverts back to the start of the AVF sequence. 
 
10.2 AS1668 Zone Processing 
 
This is typically used for an alarm zone circuit associated with supply air duct detectors. 
 These detector zones are non-latching zones. The smoke level must be such that it 
causes the detector to be in alarm for a minimum period of time. Afterwhich any outputs 
mapped to the AS1668 zone will be activated. To de-activate the mapped outputs, the 
smoke level must be such that the detector is in a non-alarm condition for a minimum 
period of time. 
 
AS1668  detector  zones  are  continually  reset  and  checked  for  an  alarm/non  alarm 
conditions. 
 
Two AS1668 zone processing cycles are available: 
 
(i)  AS1668 - 30SEC:  Minimum alarm period = 0 seconds 
        Minimum non-alarm time period = 30 seconds. 
 
(ii)  AS1668 - 60 SEC:  Minimum alarm period 0 seconds and a continuos non-alarm 
period of 65 seconds.