4020 OPERATORS MANUAL Page 35
Document No: 4020-M010 1st February, 1997 Issue 2.0
BRIGADE
DESCRIPTION
0
No test facility
1
Alarm relay ACF2 (Ct2) operates for 10 seconds
2
Alarm relay ACF2 (Ct2) operates for 15 seconds
3
Alarm relay ACF2 (Ct2) operates for 20 seconds
4
Alarm relay ACF2 (Ct2) operates for 25 seconds
5
Alarm relay ACF2 (Ct2) operates for 30 seconds
6
Alarm 1 relay ACF2 (Ct2) operates for 20 seconds Delay
for 20 seconds . Alarm 2 relay ACF3 (Ct3) operates for
20 seconds
7
Alarm 1 relay ACF2 (Ct2) operates for 20 seconds Delay
for 20 seconds. Alarm 2 relay ACF3 (Ct3) operates for 20
seconds Delay for 20 seconds
Alarm 3 relay ACF4 (Ct4) operates for 20 seconds
Table 1.2 - Available Brigade Test Options