SMA Solar Technology AG 2 Safety
Installation Manual SCCPXT-IA-D7-en-42 11
Risk of fire due to failure to observe torque specifications on live bolted connections
Failure to follow the specified torques reduces the ampacity of live bolted connections so that the contact resistances
increase. This can cause components to overheat and catch fire.
Ensure that live bolted connections are always tightened with the exact torque specified in this document.
When working on the device, use suitable tools only.
Avoid repeated tightening of live bolted connections as this may result in unacceptably high torques.
&$87,21
Risk of burns due to hot components
Some components of the Sunny Central can get very hot during operation. Touching these components can cause
burns.
Observe the warning messages on the devices.
During operation, do not touch any components marked with such warnings.
After disconnecting the PV system from voltage sources, wait until hot components have cooled down sufficiently.
Wear suitable personal protective equipment for all work on the Sunny Central.
/05*$&
Damage to the components due to dust intrusion or moisture penetration
Dust or moisture penetration can damage the Sunny Central or impair its functionality.
Do not open the Sunny Central during rainfall or humidity of more than 95%.
Only service the Sunny Central when the environment is dry and free of dust.
Do not operate the Sunny Central with the door open.
Do not connect the external supply voltage before the Sunny Central has been mounted and installed.
Switch on the circuit breaker for external supply voltage. This will activate the heating element and internal fans so
that they can switch on automatically.
If the installation or commissioning process is interrupted, mount all the panels of the Sunny Central.
Close and lock the Sunny Central.
Damage to electronic components due to electrostatic discharge
Electrostatic discharge can damage or destroy electronic components.
Observe the ESD safety regulations when working on the device.
Wear suitable personal protective equipment for all work on the device.
Discharge electrostatic charge by touching uncoated, grounded enclosure parts (e.g. near the grounding
connection on the doors). Only then is it safe to touch electronic components.