11 AC Connection SMA Solar Technology AG
52 SCCPXT-IA-D7-en-42 Installation Manual
11.2.3 Connection with Two Terminal Lugs
Figure23: Assembly of the connection with terminal lugs for terminals with double assignment
11.2.4 Connecting the AC Cables
Figure24: Dimensions of the AC connection lugs
Additionally required mounting material (not included in the scope of delivery):
☐Clean cloth
Ethanol cleaning agent
Requirement:
The AC cables must be prepared for the connection.
Position Designation
ANut
BSpring washer
CFender washer
D1 Tin-plated one-hole terminal lug
E Copper bar
FScrew M12