SMA Solar Technology AG Sunny Boy in the Island Grid System
Technical Description SI2012_2224-TEN082311 155
1. Establish communication with the Sunny Boy.
2. Go to the parameter settings.
3. Set the parameter "Default" to "Off-Grid" (stand-alone grid).
The "Off-Grid" parameter setting automatically sets the following Sunny Boy parameters to the
following values:
This completes the stand-alone grid parameter settings for the Sunny Boy.
No. Parameter Unit Value
1 I-NiTest mA Off (MSD = 0)
2 Uac-Min V 180
3 Uac-Max V 260
4 Fac-delta-
Lower range, where the Sunny Boy is active,
based on f
0
Hz -4.5 (starting from the
base frequency f
0
)
5Fac-max+
Upper range, where the Sunny Boy is active,
based on f
0
Hz +1.5 (starting at the
base frequency f
0
)
6dFac-Max
max. rate of change
Hz/s 4
7Fac-start delta
frequency increase in relation to f
0
, at which
point the power adjustment via frequency begins
Hz 1 (starting from base
frequency f
0
)
8 Fac-Limit delta
Frequency increase in relation to f
0
, at which
point the power adjustment via frequency ends.
The power of the Sunny Boy here is 0 W.
Hz 2 (starting from base
frequency f
0
)
WARNING!
Risk of lethal electric shock!
If there is an outage of the public grid there is the danger of feeding back into it
• Never operate your Sunny Backup system directly on the grid with these settings!