Appendix A
A.1
CERTIFICATIONS INFORMATION
European Directive Information
Consult www.Smar.com for the EC declarations of conformity and certificates.
Authorized representative/importer located within the Community:
Smar Europe BV De Oude Wereld 116 2408 TM Alphen aan den Rijn Netherlands
ATEX Directive 2014/34//EU - "Equipment for explosive atmospheres”
The EC-Type Examination Certificate is released by DNV GL Presafe AS (CE2460) and DEKRA Testing and
Certification GmbH (CE0158).
Designated certification body that monitors manufacturing and released QAN (Quality Assurance Notification) and
QAR (Quality Assessment Report) is Nemko AS (CE0470).
LVD Directive 2014/35/EU "Low Voltage”
According the LVD directive Annex II, electrical equipment for use in an explosive atmosphere is outside the
scope of this directive.
According to IEC standard: IEC 61010-1 Safety requirements for electrical equipment for measurement, control,
and laboratory use - Part 1: General requirements.
ROHS Directive 2011/65/EU - “Restriction of the use of certain hazardous substances in electrical and
electronic equipment”
For the evaluation of the products the following standards were consulted: EN 50581.
EMC Directive 2014/30/EU - "Electromagnetic Compatibility”
For products evaluation, the standard IEC 61326-1 were consulted and to comply with the EMC directive the
installation must follow these special conditions:
Use shielded, twisted-pair cable for powering the instrument and signal wiring.
Keep the shield insulated at the instrument side, connecting the other one to the ground.
Hazardous locations general information
Ex Standards:
IEC 60079-0 General Requirements
IEC 60079-1 Flameproof Enclosures “d”
IEC 60079-7 Increased Safe “e”
IEC 60079-11 Intrinsic Safety “i”
IEC 60079-18 Encapsulation “m”
IEC 60079-26 Equipment with equipment protection level (EPL) Ga
IEC 60079-31 Equipment dust ignition protection by enclosure "t"
IEC 60529 Classification of degrees of protection provided by enclosures (IP Code)
IEC 60079-10 Classification of Hazardous Areas
IEC 60079-14 Electrical installation design, selection and erection
IEC 60079-17 Electrical Installations, Inspections and Maintenance
IEC 60079-19 Equipment repair, overhaul and reclamation
ISO/IEC80079-34 Application of quality systems for equipment manufacture
Warning:
Explosions could result in death or serious injury, besides financial damage.
Installation of this instrument in hazardous areas must be in accordance with the local standards and type of
protection. Before proceedings with installation make sure that the certificate parameters are in accordance with
the classified hazardous area.
Maintenance and Repair
The instrument modification or replaced parts supplied by any other supplier than authorized representative of
Smar is prohibited and will void the Certification.
Marking Label
The instrument is marked with type of protection options. The certification is valid only when the type of protection
is indicated by the user. Once a particular type of protection is installed, do not reinstall it using any other type of
protection.