TP301 – Operation, Maintenance and Instructions Manual
3.4
DAMP (Damping)
Reduction function.
Inc
Increment.
Dec
Decrement.
Every parameter configuration shall be performed judiciously, since it writes the configuration
parameters on permanent basis and does not ask for confirmation by the user. Once it is
performed it is assumed to be the desired configuration.
Procedure to Calibrate the Position Transmitter
Calibration using the jumper in simple local adjustment
If the simple local adjustment is enabled, only the lower and upper position can be adjusted.
See the steps:
Step 1
Place the magnet at the lower point and insert the magnet tool in the Z orifice.
Step 2
To adjust the upper value, place the magnet in the upper point and insert the tool in the S orifice.
After this, move the device to the upper and lower position and check the measurement on the
display.
Calibration for the complete local adjustment
When the complete local adjustment is enabled the can be configured,
− the Display Indication in:
▪ Position in % (Perc);
▪ Current in mA (mA);
▪ Temperature in ºC (C);
▪ Temperature in F (F).
− the indication Direct or Reverse;
− the Lower and Upper Position.
To change from percentage indication (factory default) to any available engineering units, refer to
the configuration through configurators (see the programming tree at the configurator manual).
Configuration via Configurators
TP301 can be configured through the manual portable configurator portable manual based on
PalmOS platform. Besides, the TP301 has connectivity with FDT/DTM, CONF401 and DDCON
configuration application for desk and laptop.
For detailed information on how to install and operate the configurations software, please consult
www.smar.com for downloading the current instructions manuals.
- Configuration via manual configurator
See below the programming tree for the portable configurator based on PalmOS platform.