10 COMMISSIONING
Please make sure the following checks are made before commissioning,
a) Ensure all the connections are correct and wires diameter is suitable.
b) Ensure that the controller DC power has fuse, controller’s positive and negative connected to start
battery are correct.
c) Take proper action to prevent engine to crank success (e. g. Remove the connection wire of fuel
valve). If checking is OK, make the start battery power on; choose manual mode and controller will
executive routine.
d) Set controller under manual mode, press “start” button, genset will start. After the cranking times as
setting, controller will send signal of start failure; then press Stopto reset controller.
e) Recover the action to prevent engine to crank success (e. g. Connect wire of fuel valve), press start
button again, genset will start. If everything goes well, genset will normal running after idle running (if
idle run be set). During this time, please watch for engine’s running situations
f) If there is any other question, please contact SmartGen’s service.