HGM4100LT GENSET CONTROLLER USER MANUAL
HGM4100LT Genset Controller 2019-01-28 Version1.0 Page 16 of 48
than the set stop value, it will send stop alarm signals and the
corresponding alarm information will be displayed on LCD.
When controller detects oil pressure is lower than the set value,
it will send stop signals and the corresponding alarm information
will be displayed on LCD.
When the controller detects genset frequency is 0, it will send
stop alarm signals and the corresponding alarm information will
be displayed on LCD.
When the controller detects fuel level value is lower than the
pre-set value or the low fuel level stop input is active, it will send
stop alarm signals and the corresponding alarm information will
be displayed on LCD.
Low Coolant Level
Alarm Shutdown
When the controller detects low coolant level stop input is active,
it will send stop alarm signals and the corresponding alarm
information will be displayed on LCD.
When the sensor connected to temperature sensor, is open
circuit, and the open circuit action in parameter configuration is
selected “shutdown”, it will send stop alarm signals and the
corresponding alarm information will be displayed on LCD.
When the sensor connected to oil pressure sensor, is open
circuit, and the open circuit action in parameter configuration is
selected “shutdown”, it will send stop alarm signals and the
corresponding alarm information will be displayed on LCD.
When the sensor connected to fuel level sensor, is open circuit,
and the open circuit action in parameter configuration is selected
“shutdown”, it will send stop alarm signals and the corresponding
alarm information will be displayed on LCD.
When the temperature sensor connected to the programmable
sensor port, is open circuit, and the open circuit action in
parameter configuration is selected “shutdown”, it will send stop
alarm signals and the corresponding alarm information will be
displayed on LCD.
When the pressure sensor connected to the programmable
sensor port, is open circuit, and the open circuit action in
parameter configuration is selected “shutdown”, it will send stop
alarm signals and the corresponding alarm information will be
displayed on LCD.
When the liquid level sensor connected to the programmable