HGM9520N Genset Paralleled Controller User Manual Page 10 of 111
5A DC30V DC power supply output (relay output)
5A DC30V DC power supply output (relay output)
5A DC30V DC power supply output (relay output)
8A AC250V volt-free output (relay output)
8A AC250V volt-free output (relay output)
8A AC250V volt-free output (relay output)
1A DC30V DC power supply output (transistor output)
1A DC30V DC power supply output (transistor output)
Low limit voltage is 1.2V; high limit voltage is 60V;
Isolated, half-duplex, 9600 baud rate, maximum communication
length 1000m
Isolated, maximum communication length 250m; applying Belden
9841 cable or the equivalence
5 - 8 Hz: ±7.5 mm
8 - 500 Hz: 2 g
IEC 60068-2-6
50g, 11ms, half-sine, complete shock test from three directions, and
18 times shock for each test
IEC 60068-2-27
25g, 16ms, half-sine
IEC 60255-21-2
According to EN 61010-1 installation category (over voltage category)
III, 300V, pollution class 2, altitude 3000m
Temperature: (-25~+70)°C Relative Humidity: (20~93)%RH
Front Enclosure: IP65 when rubber-ring gasket is installed between
the enclosure and the control panel
Rear Enclosure: IP20
Apply AC2.2kV voltage between high voltage terminal and low voltage
terminal and the leakage current is not more than 3mA within 1min.