HGM9520N Genset Paralleled Controller User Manual Page 54 of 111
6 WIRING CONNECTION
Fig. 3 HGM9520N Controller Rear Panel Drawing
Table 15 Terminal Connection Description
Connect with starter battery negative.
Connect with starter battery positive. If wire length is
over 30m, it’s better to double wires in parallel. Max. 20A
fuse is recommended.
Connect with B+ via emergency stop button.
B+ is supplied by 3 points, rated 16A.
B+ is supplied by 3 points, rated 16A.
Connect to starter coil.
B+ is supplied by 2 points, rated 5A.
B+ is supplied by 2 points, rated 5A.
B+ is supplied by 2 points, rated 5A.
B+ is supplied by 2 points, rated 1A.
B+ is supplied by 2 points, rated 1A.
Connect with Charger D+ (WL) terminal. If this terminal
doesn’t exist, hang it in the air.
Ground connected is active (B-).