HGM9520N Genset Paralleled Controller User Manual Page 103 of 111
17 CONNECTIONS OF CONTROLLER AND J1939 ENGINE
17.1 CUMMINS ISB/ISBE
Table 22 Connector B
Connected with starter coil directly;
Expansion 30A relay;
providing battery voltage for
terminal 01, 07, 12, 13.
ECU power;
Set output 1 as “ECU power”.
CAN communication shielding line
(connected with ECU terminal only).
Impedance 120Ω connecting line is
recommended.
Impedance 120Ω connecting line is
recommended.
Engine type: Cummins ISB.
17.2 CUMMINS QSL9
Suitable for CM850 engine control module.
Table 24 50-Pin Connector
Connected to starter coil directly.
CAN communication shielding line
(connected with ECU terminal only).
Using impedance 120Ω connecting line.
Using impedance 120Ω connecting line.
Engine type: Cummins-CM850.