HGM9520N Genset Paralleled Controller User Manual Page 59 of 111
pre-heating earlier according to the set
conditions.
Sensors are available, and when it is above
the set value, it shall end the pre-heating.
0: Disable
1: Enable
When it is enabled, the controller will stop
pre-heating earlier according to the set
conditions.
Sensor is available, and when it is above the
set value, it shall end the start idle period.
Default: conventional engine (not ECU)
When the controller is connected to J1939
engine, choose the corresponding type.
Tooth number of the engine, for judging of
starter separation conditions and
inspecting of engine speed. See the
installation instructions.
Offer standard to judge over/under/loading
speed.
Set value is percentage of rated speed.
Controller detects when it is ready to load.
It won’t switch on when speed is under
loading speed.
Loss of Speed
Signal Delay
Time from detecting 0 speed to action
confirm.
Loss of Speed
Signal Action
0: None; 1: Warning; 2: Block; 3: Safety Trip;
4: Safety Trip and Stop; 5: Trip; 6: Trip and
Stop; 7: Shutdown.
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
0: Disable 1: Enable
Setting value is rated speed percentage.
Return value is rated speed percentage.
Delay value
Action
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
0: Disable 1: Enable
Setting value is rated speed percentage.
Return value is rated speed percentage.
Delay value
Action
(0~1)
(0~200.0)%
(0~200.0)%
0: Disable 1: Enable
Setting value is rated speed percentage.
Return value is rated speed percentage.