HGM9520N Genset Paralleled Controller User Manual Page 61 of 111
frequency; when generator frequency is
higher than the set value, starter will be
disconnected. See the below installation
instruction.
Percentage of the rated speed; when
generator speed is higher than the set
value, starter will be disconnected. See the
installation instruction.
When generator oil pressure is higher than
the set value, starter will be disconnected.
See the installation instruction.
0: None; 1: Warning; 2: Block; 3: Safety Trip;
4: Safety Trip and Stop; 5: Trip; 6: Trip and
Stop; 7: Shutdown.
0: 3P4W; 1: 3P3W;
2: 2P3W; 3: 1P2W.
Numbers of generator pole, used for
calculating engine speed when there is not
speed sensor.
To offer standards for detecting of gens’
over/under voltage and loading voltage. (It
is primary voltage when voltage
transformer is used; it is line voltage when
AC system is 3P3W while it is phase
voltage when other AC system is used).
Percentage of generator rated voltage; it is
detected when the controller prepares to
load; when the generating voltage is below
the load voltage. It won’t enter normally
running period.
Offer standards for detecting
over/under/load frequency.
Percentage of generator rated frequency;
detected when controller prepares to take
load; when generator frequency is under
load frequency, it won’t enter normal
running.
(0~1)
(0~200.0)%
(0~200.0)%
0: Disable 1: Enable
Set value is gen rated volt percentage.
Return value is gen rated volt percentage.