Chapter 5 Display and setting of various functions
HRS-R Series 5.18 Accumulated time reset function
3. Select from the table below with [▲] key or [▼] key, and confirm by pressing
“SEL”. Select , then the accumulated operating time of the pump is reset. The
display returns to the main menu.
Table 5.18-2 List of set value
Initial value
(Default setting)
Pump accumulated operating time is reset
Fun motor accumulated operating time reset
4. Press the [SEL] key once.
The set screen of fun motor accumulated operating time reset is displayed on the digital
display.
5. Select from the table below with [▲] key or [▼] key, and confirm by pressing
“SEL”. Select , then the accumulated operating time of the fan motor is reset.
The display returns to the main menu.
Table 5.18-3 List of set value
Initial value
(Default setting)
Fan motor accumulated operating time is
reset
Compressor accumulated operating time reset
6. Press the [SEL] key once.
The set screen of compressor accumulated operating time reset is displayed on the
digital display.
7. Select from the table below with [▲] key or [▼] key, and confirm by pressing
“SEL”. Select , then the accumulated operating time of the compressor is reset.
The display returns to the main menu.
Table 5.18-4 List of set value
Initial value
(Default setting)
Compressor accumulated operating time is
reset