HRX-OM-W058
Chapter 8 Control, Inspection and Cleaning
8.3 Consumables HRS-R Series
8-6
8.2.5 Inspection for winter season
Prevention of freezing of circulating fluid
The product can prevent freezing of the circulating fluid during winter or at night.
If there is a risk of freezing due to a change of installation conditions and operating
environment (operating time, weather etc.), conduct the following operations in
advance.
Anti-freezing function (automatic pump operating function)
When the circulating fluid temperature reaches 3
o
C, the pump will start
automatically.
The operation of pump will heat the circulating fluid with its power.
Then, when the circulating fluid temperature reaches 5
o
C, the pump will
stop automatically.
As a result, the circulating fuid temperature is kept between 3 and 5
o
C, and
can be prevented from freezing.
This function does not prevent the freezing of the automatic fluid filling circuit
(when the option is selected). The measure for the automatic fluid filling
circuit is taken by customer.
For details refer to “5.11 Anti-freezing function”.
1. Keep the power supply on. (RUN lamp flashes at 2sec. intervals.)
2. Fully open the valve and manual relief valve installed by the user, to ensure the
circulating fluid will be able to circulate when the pump starts automatically.
8.3 Consumables
Replace the following parts depending on their condition.
Table 8-5 Consumables
Part number
Name
Qty.
Remarks
HRS-FL003
Dustproof filter
1
For spare (5 filters per set)
HRG-S0211
Mechanical seal set
1
For option T (High pressure pump)