Chapter 3 Transport and Setting Up
HRS-R Series 3.4 Piping
3-21
How to connect piping
Tighten the piping to circulating fluid outlet / return port.
Fig. 3-13 Tightening of piping
Recommended piping circuit
Fig. 3-14 Recommended piping circuit
No. Description Size Recommended part no. Note
1 Valve Rc1/2 - -
2
Filter
Rc1/2
20μm
HRS-PF003
If foreign objects with a size of 20 μm or more are
likely to enter, install the particle filter.
3 Flow meter 0 to 50L/min - -
4 Pressure gauge 0 to 1.0MPa - -
5 Others (pipe, hose, etc.) ø15 or more - -
Outlet Rc1/2
Return Rc1/2
Sealant material
Piping port
Circulating fluid
return port
1
1
1
1
4
1
3
2
4
Circulating fluid
outlet
Thermo-chiller
User's
equipment

Table of Contents