Chapter 4 Starting the Product
4.3 Preparation of circulating fluid HRS-R Series
4-4
2. Press the [RESET] key ([▼] and [▲] keys simultaneously) to stop the alarm buzzer.
Fig. 4-5 Alarm receipt
3. Open the tank lid and supply the circulating fluid up to the “H” mark on the tank.
Fig. 4-6 Filling of Circulating Fluid
Flash
Press together
ON
Be sure to reset the alarm on the operation display panel of the alarm. Alarm reset
is not accepted from any screen except the alarm display menu. Refer to 5.2.1 Key
operations.
Tank lid
Fluid level
Circulating fluid fill