MASTERYS BC 100-120 kVA - Ref.: IOMMASBCXX07-EN 05
ENGLISH
8. TROUBLESHOOTING
8.3.2. Fans
The lifetime of fans used to cool the power parts is dependent on usage and environmental conditions (temperature, dust).
Preventive replacement by an authorised technician is recommended within four years (in normal operating conditions).
Fans must be replaced by SOCOMEC technicians when required.
8.3.3. Capacitors
The equipment houses electrolytic capacitors (used in the rectifi er and inverter section) and fi ltering capacitors (used in the output
section), whose lifetime is dependent on usage and environmental conditions.
The average expected lifetime of these components is shown below:
• Electrolytic capacitors: 5 years;
• Filtering capacitors: 7 years.
The actual condition of components is verifi ed during preventive maintenance.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec Masterys BC and is the answer not in the manual?

socomec Masterys BC Specifications

General IconGeneral
Frequency50/60 Hz
Power factor0.9
Protection DegreeIP20
Input Voltage400 V three-phase + N
Output Voltage400 V three-phase + N
EfficiencyUp to 96%
Battery TypeVRLA
Operating Temperature0 to +40 °C
Relative Humidity0% to 95% (non-condensing)
CoolingForced air
Communication InterfaceRS232, USB
DimensionsVaries by model (e.g., 650 x 800 x 1200 mm for 20 kVA)
WeightVaries by model (e.g., 300 kg for 20 kVA)
TopologyDouble conversion